Induction Effect in Chilled Beams and Diffusers

October 23, 2020
Induction Effect in Chilled Beams and Diffusers

INDUCTION EFFECT IN ACTIVE CHILLED BEAM UNITS

In Chilled Beams, the term “induction” is used to describe the process of primary air being blown under pressure through a nozzle, which then entrains return or plenum air at the nozzle exit.

ekil 1

Figure 1: Induction effect in a chilled beam unit

The ratio of the entrained air (induced air quantity Q) to the primary air quantity is called the induction ratio.

formül1

Before contacting the air blown from the nozzle, the induced air is drawn over a coil that heats or cools the air. The amount of energy transferred by the coil depends on various factors such as the induced air temperature, water supply temperature, the volume of induced air passing over the coil, and the coil surface area.

ekil 2

Figure 2: The process of primary air being blown under pressure from a nozzle

When designing a chilled beam system, transfer effectiveness is a frequently used parameter. This is the ratio of the primary air volume to the heating or cooling energy transferred by the coil.

formül2

Transfer effectiveness is related to the overall HVAC system efficiency. Since the required air is significantly more than it can store due to the lower amount of thermal energy, transporting thermal energy with water requires less energy than transporting it with air. Several recent building designs have shown a potential gain of 10-15% in energy savings. Potential savings are higher but are limited by the system choices made by the designer and primary air requirements. To minimize energy consumption, the primary airflow rate should not exceed the fresh air requirements.

Water is a much more efficient option for transferring energy.

When designing a building's HVAC system, knowing the induction ratio for chilled beams can be beneficial. For example, when selecting an active chilled beam for use in a patient room, ASHRAE Standard 170 recommends a minimum of six air changes, at least two of which should be fresh air. All six air changes can be fresh air, but in designs where energy efficiency is high, fresh air should be limited to a minimum of two changes. This means the designer should choose an induction ratio of 2 m³/h of induced air for 1 m³/h of primary air to meet the required six air changes.

For an active induction unit, the induction ratio is typically determined by calculating an energy balance across the unit. Essentially, the total energy transferred to the induced air on the water side is used to determine the induced airflow rate. The determination of the induction ratio is mostly carried out using air temperature measurements. After knowing the primary air temperature, induced air temperature, and discharge (mixed) air temperature, the induction ratio can be calculated. The discharge air temperature depends on the number and location of primary air nozzles along the length of the discharge slots and should be determined in a test environment, not on-site. This will ensure accurate measurement of the discharge air temperature.

INDUCTION EFFECT IN DIFFUSERS

Unlike an induction unit, the induction ratio of a ceiling diffuser is determined by the volume of air blown from the diffuser's opening, not by the volume of air entering an opening (Figure 3). As the supply air blown from the diffuser opening moves, its velocity slows down due to the mass of air entrained and added to this air. To determine the volume of induced air, a fixed distance from the diffuser must be established, because as the distance from the diffuser increases, the volume of entrained air increases, and the induction ratio increases. Once a distance is established, the volume of entrained air can be estimated using the supply air temperature, entrained (room) air temperature, and mixed air temperature (at the determined distance).

ekil 5

Figure 3: Entrained air along the diffuser's throw path

The mixed air temperature is not an easily determinable value, as there can be significant variations in the moving air layer. This layer is less than 1cm thick near the discharge point but can be thicker depending on the diffuser type. In some cases, the layer may even be detached from the ceiling. Better induction ratios can be achieved with diffusers that have regular throw patterns at high discharge velocities and are thin.

A better reference for evaluating the effectiveness of a ceiling diffuser would be the Air Diffusion Performance Index (ADPI). ADPI is a single-number rating index for a diffuser with a specified supply airflow rate, supply air temperature, and cooling load. This depends on the air velocity in the occupied zone and the draft temperature in the area.

Example of induction use in project design:

In the multi-purpose complex project example below, air distribution is provided by two different diffuser systems.

ekil 3

Figure 4: Application example of the induction effect of a jet nozzle diffuser

  1. Primary air thrown at high velocity to the center of the field from the upper part of the stands with jet nozzle diffusers.
  2. Primary air supplied at low velocity towards the field from the lower part of the stands with displacement diffusers.

In this design; the high-velocity air thrown from the top of the stands with a jet nozzle also induces the ambient air in the lower sections and mixes it with the jet nozzle air. This way, it carries the primary air supplied from the lower part of the stands upwards along the seating area, ensuring conditioned fresh air circulation for the spectator section.

ekil 4

Figure 5: Application example of the induction effect of a jet nozzle diffuser-2

Sources: Price Industries Limited

Prepared by: Samet Menteş – Ender Bilgin